Guided wave radar level gauge installation precautions:
The 1-bar probe and cable probe should be installed as far as possible from the feed port to avoid wear;
The 2-bar probe and cable probe should be kept at a certain distance from the tank wall and the tank bottom, and should not touch the metal tank wall and the tank bottom;
3 When the tank wall is adhered, the distance between the probe and the tank wall is at least 100 mm;
4 Minimum distance between the end of the probe and the bottom of the tank: cable probe (150mm); rod probe (50mm); coaxial rod probe (10mm);
5-pole probes and cable probes should be installed as far as possible from the installed equipment more than 300mm, such as tuning fork brackets, to avoid interference;
6 Select the appropriate installation location to avoid bending the probe during installation or operation;
7 Before installation, check the probe for damage. When installing, it is best to do it when it is empty;
8 When installing outdoors, it is recommended to use such a protective cover;
Concerned about surprises
Label: Guided wave radar level gauge installation precautions
Previous: Key points in the operation of the turn-over machine Next: How to make the self-priming pump flow head work stably
A Semi-Flush Mount is a type of Lighting Fixture that is installed on the ceiling and hangs down slightly, but not as far as a Pendant Light. It is a popular choice for rooms with low ceilings, as it provides ample Lighting Product without taking up too much vertical space. Semi-Flush Mount Lighting come in a variety of styles and designs, from modern and sleek to more traditional and ornate. Semi-Flush Light are typically easy to install and can be used in a variety of settings, including bedrooms, living rooms, and kitchens.
Semi-Flush,Semi-Flush Mount,Semi-Flush Light,Semi Flush Mount,Semi-Flush Mount Lighting,Ceiling Mount Lighting,Ceiling Flush Mount Light Fixture,Led Ceiling Flush Mount Light
Zhengdong Lighting Co., Ltd. , https://www.sundint.com